Danfoss VLT AQUA Drive FC 202 FC-202P90KT6E21HXXGXXXXSXXXXA0BXCXXXXDX
137L7687

Danfoss 137L7687 - VLT AQUA Drive FC 202 (90 kW / 125 HP, IP21, 525-600V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (P90K) 90 KW / 125 HP,
  • Three phase, 525 - 600 VAC,IP21 / Type 1
  • No RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: C2
  • PROFIBUS DP MCA 101, No B Option
  • No C1 option, No D option
Model code:
FC-202P90KT6E21HXXGXXXXSXXXXA0BXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingP90K(P90K) 90 KW / 125 HP
PhaseTThree phase
Mains Voltage6525 - 600 VAC
EnclosureE21IP21 / Type 1
RFI FilterHXNo RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 150% (HO) [KW]75
Power 110% (NO) [KW]90
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA130
Power Loss NO [W]1800
Power Loss HO [W]1500
Continuous Current (NO) [A]137
Intermittent Current (NO) [A]151
Continuous Current (NO) [A]131
Intermittent Current (NO) [A]144
Continuous Current (HO) [A]105
Intermittent Current (HO) [A]158
Continuous Current (HO) [A]100
Intermittent Current (HO) [A]150

Technical data

Motor power90 kW / 125 HP
Mains voltage525 - 600 VAC
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeC2
RFI filterNone
Brake chopperNo
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current137 A
Continuous current (high line)131 A
Intermittent output current151 A
Continuous current (high overload)105 A
Apparent power130 kVA
Power loss1800 W
Power, normal overload90 kW
Power, high overload75 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight55.54 kg
Gross weight58.88 kg
Packed volume232.7 L
EAN5715253553047
ECCN (EU)Y901
ECCN (US)3A999.a

Documents