Danfoss VLT AutomationDrive FC 302 FC-302P4K0T5Y55H1XGX1XXSXXXXANBXCXXXXDX
137U1385

Danfoss 137U1385 - VLT AutomationDrive FC 302 (4 kW / 5 HP, IP55, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P4K0) 4.0 KW / 5.0 HP,
  • Three phase, 380 - 500 VAC,IP55 / Type 12 Backplate
  • (H1) RFI Class A1/B (C1)
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: A4
  • EtherNet/IP MCA 121, No B Option
  • No C1 option, No D option
Model code:
FC-302P4K0T5Y55H1XGX1XXSXXXXANBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP4K0(P4K0) 4.0 KW / 5.0 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureY55IP55 / Type 12 Backplate
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionANEtherNet/IP MCA 121
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeA4
Power 160% (HO) [KW]4
Height [mm]391,0
Width w/ no C options [mm]200,0
Depth [mm]177,0
Depth with Option A/B [mm]177,0
kVA6.93
Power Loss HO [W]124
Continuous Current (HO) [A]10
Intermittent Current (HO) [A]16
Continuous Current (HO) [A]8.2
Intermittent Current (HO) [A]13.1

Technical data

Motor power4 kW / 5 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP55 / Type 12 Backplate
Frame sizeA4
RFI filterClass A1/B (EMC C1)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionMains Disconnect
FieldbusEtherNet/IP MCA 121
Product typeFrequency converter
Continuous output current10 A
Intermittent output current16 A
Apparent power6.93 kVA
Power loss124 W
Power, high overload4 kW
Height391 mm
Width200 mm
Depth177 mm
Depth with A/B options177 mm
Net weight9.11 kg
Gross weight9.85 kg
EAN5715253696928
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137U1385 are available on request. Ask for documents →

Other 4 kW / 5 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.