Danfoss VLT HVAC Drive FC 102 FC-102P75KT4E55H1XGX3XXLX1XXAKBKCXRXXDX
137U6613

Danfoss 137U6613 - VLT HVAC Drive FC 102 (75 kW / 100 HP, IP55, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P75K) 75 KW / 100 HP,
  • Three phase, 380 - 480 VAC,IP55 / Type 12
  • (H1) RFI Class A1/B (C1)
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, Mains Disconnect + Fuse
  • Condition Based Monitoring CBM
  • Frame: C2
  • MCA 125 BACnet/IP, MCB-101 General purp. I/O
  • MCB-113 Ext. Relay Card, No D option
Model code:
FC-102P75KT4E55H1XGX3XXLX1XXAKBKCXRXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP75K(P75K) 75 KW / 100 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE55IP55 / Type 12
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseLX1XCondition Based Monitoring CBM
Software Language PackXStandard Language Pack
A OptionAKMCA 125 BACnet/IP
B OptionBKMCB-101 General purp. I/O
C0 Option MCOCXNo C0 option
C1 OptionRMCB-113 Ext. Relay Card
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 110% (NO) [KW]75
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA102
Power Loss NO [W]1384
Continuous Current (NO) [A]147
Intermittent Current (NO) [A]162
Continuous Current (NO) [A]130
Intermittent Current (NO) [A]143

Technical data

Motor power75 kW / 100 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP55 / Type 12
Frame sizeC2
RFI filterClass A1/B (EMC C1)
Brake chopperNo
Control panelGraphical LCP
PCB coatingUncoated
Mains optionMains Disconnect + Fuse
FieldbusMCA 125 BACnet/IP
Product typeFrequency converter
Continuous output current147 A
Continuous current (high line)130 A
Intermittent output current162 A
Apparent power102 kVA
Power loss1384 W
Power, normal overload75 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight60.01 kg
Gross weight63.35 kg
Packed volume248.1 L
EAN5715253751115
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137U6613 are available on request. Ask for documents →

Other 75 kW / 100 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.