Danfoss VLT AutomationDrive FC 302 FC-302P11KT2E55H1BGX1XXSXXXXALBXCXXXXD0
137U8726

Danfoss 137U8726 - VLT AutomationDrive FC 302 (11 kW / 15 HP, IP55, 200-240V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P11K) 11 KW / 15 HP,
  • Three phase, 200 - 240 VAC,IP55 / Type 12
  • (H1) RFI Class A1/B (C1)
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: B2
  • PROFINET MCA 120, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-302P11KT2E55H1BGX1XXSXXXXALBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP11K(P11K) 11 KW / 15 HP
PhaseTThree phase
Mains Voltage2200 - 240 VAC
EnclosureE55IP55 / Type 12
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionALPROFINET MCA 120
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeB2
Power 160% (HO) [KW]11
Power 110% (NO) [KW]15
Height [mm]664,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
kVA16.6
Power Loss NO [W]602
Power Loss HO [W]463
Continuous Current (NO) [A]59.4
Intermittent Current (NO) [A]65.3
Continuous Current (HO) [A]46.2
Intermittent Current (HO) [A]73.9

Technical data

Motor power11 kW / 15 HP
Mains voltage200 - 240 VAC
PhaseThree-phase
Protection ratingIP55 / Type 12
Frame sizeB2
RFI filterClass A1/B (EMC C1)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionMains Disconnect
FieldbusPROFINET MCA 120
Product typeFrequency converter
Continuous output current59.4 A
Intermittent output current65.3 A
Continuous current (high overload)46.2 A
Apparent power16.6 kVA
Power loss602 W
Power, normal overload15 kW
Power, high overload11 kW
Height664 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight31.16 kg
Gross weight34.72 kg
Packed volume144.7 L
EAN5715253772448
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137U8726 are available on request. Ask for documents →

Other 11 kW / 15 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery