Danfoss VLT AQUA Drive FC 202 FC-202P11KT4P55H1XGC1OXLX1XXALBXCXXXXDX
137X4460

Danfoss 137X4460 - VLT AQUA Drive FC 202 (11 kW / 15 HP, IP55, 380-480V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (P11K) 11 KW / 15 HP,
  • Three phase, 380 - 480 VAC, IP55 / Type12 Backplate
  • (H1) RFI Class A1/B (C1)
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Condition Based Monitoring CBM
  • Frame: B1
  • PROFINET MCA 120, No B Option
  • No C1 option, No D option
Model code:
FC-202P11KT4P55H1XGC1OXLX1XXALBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingP11K(P11K) 11 KW / 15 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureP55IP55 / Type12 Backplate
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AOMetric thread cable entry
Adaptation BXNo adaptation
Software ReleaseLX1XCondition Based Monitoring CBM
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeB1
Height [mm]494,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
Power 160% (HO) [KW]7.5
Power 110% (NO) [KW]11
kVA16.6
Power Loss HO [W]291
Power Loss NO [W]392
Continuous Current (HO) [A]16
Intermittent Current (HO) [A]25.6
Continuous Current (HO) [A]14.5
Intermittent Current (HO) [A]23.2
Continuous Current (NO) [A]24
Intermittent Current (NO) [A]26.4
Continuous Current (NO) [A]21
Intermittent Current (NO) [A]23.1

Technical data

Motor power11 kW / 15 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP55 / Type12 Backplate
Frame sizeB1
RFI filterClass A1/B (EMC C1)
Brake chopperNo
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
Product typeFrequency converter
Continuous output current24 A
Continuous current (high line)21 A
Intermittent output current26.4 A
Continuous current (high overload)16 A
Apparent power16.6 kVA
Power loss392 W
Power, normal overload11 kW
Power, high overload7.5 kW
Height494 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight22.4 kg
Gross weight26.02 kg
Packed volume105.7 L
EAN5715253831275
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137X4460 are available on request. Ask for documents →

Other 11 kW / 15 HP variants in VLT AQUA Drive FC 202

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.