Danfoss VLT HVAC Drive FC 102 FC-102N200T4E5MH2TGC3XQSXXXXA0BXCXXXXD0
137X6801

Danfoss 137X6801 - VLT HVAC Drive FC 102 (200 kW / 300 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N200) 200 KW / 300 HP,
  • Three phase, 380 - 480 VAC, IP54/Type 12+main shield
  • RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: D7H
  • PROFIBUS DP MCA 101, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102N200T4E5MH2TGC3XQSXXXXA0BXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN200(N200) 200 KW / 300 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE5MIP54/Type 12+main shield
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BQHeat-sink access
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeD7H
Height [mm]1978,0
Width w/ no C options [mm]420,0
Depth [mm]386,0
Depth with Option A/B [mm]386,0
Power 110% (NO) [KW]200
kVA274
Power Loss NO [W]4109
Power Loss NO [W]3561
Continuous Current (NO) [A]395
Intermittent Current (NO) [A]435
Continuous Current (NO) [A]361
Intermittent Current (NO) [A]397

Technical data

Motor power200 kW / 300 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54/Type 12+main shield
Frame sizeD7H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
Product typeFrequency converter
Continuous output current395 A
Continuous current (high line)361 A
Intermittent output current435 A
Apparent power274 kVA
Power loss4109 W
Power, normal overload200 kW
Height1978 mm
Width420 mm
Depth386 mm
Depth with A/B options386 mm
Net weight200 kg
Gross weight200.3 kg
Packed volume956.2 L
EAN5715253855196
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137X6801 are available on request. Ask for documents →

Other 200 kW / 300 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.