Danfoss VLT AutomationDrive FC 302 FC-302N200T5E54H2BGCXXXSXXXXALB7CXXXXDX
137X8124

Danfoss 137X8124 - VLT AutomationDrive FC 302 (200 kW / 300 HP, IP54, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (N200) 200 KW / 300 HP,
  • Three phase, 380 - 500 VAC, (E54) IP54 / Type 12
  • RFI Filter
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: D7H
  • PROFINET MCA 120, MCB-151 Safe Option HTL
  • No C1 option, No D option
Model code:
FC-302N200T5E54H2BGCXXXSXXXXALB7CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingN200(N200) 200 KW / 300 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionB7MCB-151 Safe Option HTL
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeD7H
Power 150% (HO) [KW]200
Power 110% (NO) [KW]250
Power Loss HO [W]4039
Power Loss HO [W]3575
Power Loss NO [W]4566
Power Loss NO [W]5137
kVA274
Continuous Current (HO) [A]395
Intermittent Current (HO) [A]592
Continuous Current (HO) [A]361
Continuous Current (NO) [A]443
Intermittent Current (HO) [A]542
Intermittent Current (NO) [A]528
Continuous Current (NO) [A]480
Intermittent Current (NO) [A]487
Height [mm]1978,0
Width w/ no C options [mm]420,0
Depth [mm]386,0
Depth with Option A/B [mm]386,0

Technical data

Motor power200 kW / 300 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeD7H
RFI filterClass A2 (EMC C3)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
Product typeFrequency converter
Continuous output current443 A
Continuous current (high line)480 A
Intermittent output current528 A
Continuous current (high overload)395 A
Apparent power274 kVA
Power loss4566 W
Power, normal overload250 kW
Power, high overload200 kW
Height1978 mm
Width420 mm
Depth386 mm
Depth with A/B options386 mm
Net weight200 kg
Gross weight200.3 kg
Packed volume432.5 L
EAN5715253868745
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137X8124 are available on request. Ask for documents →

Other 200 kW / 300 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.