Danfoss VLT HVAC Drive FC 102 FC-102P15KT4P55H2TGX1XXSXXXXAQB2CXXXXDX
167F1300

Danfoss 167F1300 - VLT HVAC Drive FC 102 (15 kW / 20 HP, IP55, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P15K) 15 KW / 20 HP,
  • Three phase, 380 - 480 VAC, IP55 / Type12 Backplate
  • RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Not coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: B1
  • Modbus TCP MCA 122, MCB-112 PTC Therm. Card
  • No C1 option, No D option
  • ATEX: II (2) G [Ex eb Gb] [Ex db Gb] / II (2) D [Ex tb Db]
Model code:
FC-102P15KT4P55H2TGX1XXSXXXXAQB2CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP15K(P15K) 15 KW / 20 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureP55IP55 / Type12 Backplate
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionB2MCB-112 PTC Therm. Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeB1
Height [mm]494,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
Power 110% (NO) [KW]15
kVA22.2
Power Loss NO [W]392
Continuous Current (NO) [A]32
Intermittent Current (NO) [A]35.2
Continuous Current (NO) [A]27
Intermittent Current (NO) [A]29.7
ATEX Marking 1ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2db Gb] / II (2) D [Ex tb Db]

Technical data

Motor power15 kW / 20 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP55 / Type12 Backplate
Frame sizeB1
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionMains Disconnect
Product typeFrequency converter
Continuous output current32 A
Continuous current (high line)27 A
Intermittent output current35.2 A
Apparent power22.2 kVA
Power loss392 W
Power, normal overload15 kW
Height494 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight21.61 kg
Gross weight25.23 kg
Packed volume105.7 L
EAN5715253901459
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167F1300 are available on request. Ask for documents →

Other 15 kW / 20 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.