Danfoss VLT HVAC Drive FC 102 FC-102N200T4E20H4BGCXXXSXXXXANBXCXXXXD0
167F1496

Danfoss 167F1496 - VLT HVAC Drive FC 102 (200 kW / 300 HP, IP20, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N200) 200 KW / 300 HP,
  • Three phase, 380 - 480 VAC, (E20) IP20 / Chassis
  • RFI class A1 (C2)
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: D4H
  • EtherNet/IP MCA 121, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102N200T4E20H4BGCXXXSXXXXANBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN200(N200) 200 KW / 300 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE20(E20) IP20 / Chassis
RFI FilterH4RFI class A1 (C2)
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeD4H
Height [mm]1122,0
Height w/ Regen/Loadshare [mm]1268,0
Width w/ no C options [mm]350,0
Depth [mm]375,0
Depth with Option A/B [mm]375,0
Power 110% (NO) [KW]200
kVA274
Power Loss NO [W]4109
Power Loss NO [W]3561
Continuous Current (NO) [A]395
Intermittent Current (NO) [A]435
Continuous Current (NO) [A]361
Intermittent Current (NO) [A]397

Technical data

Motor power200 kW / 300 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP20 / Chassis
Frame sizeD4H
RFI filterClass A1 (EMC C2)
Brake chopperYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
Product typeFrequency converter
Continuous output current395 A
Continuous current (high line)361 A
Intermittent output current435 A
Apparent power274 kVA
Power loss4109 W
Power, normal overload200 kW
Height1122 mm
Height with regen/loadshare1268 mm
Width350 mm
Depth375 mm
Depth with A/B options375 mm
Net weight125 kg
Gross weight125.3 kg
Packed volume370.2 L
EAN5715253903415
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167F1496 are available on request. Ask for documents →

Other 200 kW / 300 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.