Danfoss VLT HVAC Drive FC 102 FC-102N355T4E54H2TGC3XXSXXXXA0B0CXXXXDX
167F3339

Danfoss 167F3339 - VLT HVAC Drive FC 102 (355 kW / 500 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N355) 355 KW / 500 HP,
  • Three phase, 380 - 480 VAC, (E54) IP54 / Type 12
  • RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: E1H
  • PROFIBUS DP MCA 101, MCB-109 I/O, RTC Back-up
  • No C1 option, No D option
Model code:
FC-102N355T4E54H2TGC3XXSXXXXA0B0CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN355(N355) 355 KW / 500 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionB0MCB-109 I/O, RTC Back-up
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeE1H
Height [mm]2000,0
Width w/ no C options [mm]600,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
Power 110% (NO) [KW]355
kVA456
Power Loss NO [W]6928
Power Loss NO [W]5910
Continuous Current (NO) [A]658
Intermittent Current (NO) [A]724
Continuous Current (NO) [A]590
Intermittent Current (NO) [A]649

Technical data

Motor power355 kW / 500 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeE1H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
Product typeFrequency converter
Continuous output current658 A
Continuous current (high line)590 A
Intermittent output current724 A
Apparent power456 kVA
Power loss6928 W
Power, normal overload355 kW
Height2000 mm
Width600 mm
Depth510 mm
Depth with A/B options510 mm
Net weight295 kg
Gross weight295.3 kg
Packed volume1372.4 L
EAN5715253923321
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167F3339 are available on request. Ask for documents →

Other 355 kW / 500 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.