Danfoss VLT HVAC Drive FC 102 FC-102N250T4E5MH2TLC7XQLXX4XAXBXCXXXXD1
167F4207

Danfoss 167F4207 - VLT HVAC Drive FC 102 (250 kW / 350 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N250) 250 KW / 350 HP,
  • Three phase, 380 - 480 VAC, IP54/Type 12+main shield
  • RFI Filter
  • Safe Stop
  • Graphical LCP + USB
  • Coated PCB, Fuse
  • Flux
  • Frame: D2H
  • No A Option, No B Option
  • No C1 option, MCB-117 Real time clock option
Model code:
FC-102N250T4E5MH2TLC7XQLXX4XAXBXCXXXXD1
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN250(N250) 250 KW / 350 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE5MIP54/Type 12+main shield
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPLGraphical LCP + USB
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BQHeat-sink access
Software ReleaseLXX4Flux
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD1MCB-117 Real time clock option
Frame SizeD2H
Height [mm]1060,0
Width w/ no C options [mm]420,0
Depth [mm]378,0
Depth with Option A/B [mm]378,0
Power 110% (NO) [KW]250
kVA333
Power Loss NO [W]5129
Power Loss NO [W]4558
Continuous Current (NO) [A]480
Intermittent Current (NO) [A]528
Continuous Current (NO) [A]443
Intermittent Current (NO) [A]487

Technical data

Motor power250 kW / 350 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54/Type 12+main shield
Frame sizeD2H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP + USB
PCB coatingCoated PCB
Mains optionIntegrated Fuse
Product typeFrequency converter
Continuous output current480 A
Continuous current (high line)443 A
Intermittent output current528 A
Apparent power333 kVA
Power loss5129 W
Power, normal overload250 kW
Height1060 mm
Width420 mm
Depth378 mm
Depth with A/B options378 mm
Net weight125 kg
Gross weight125.3 kg
Packed volume370.2 L
EAN5715253932187
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167F4207 are available on request. Ask for documents →

Other 250 kW / 350 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.