Danfoss VLT HVAC Drive FC 102 FC-102P37KT4P66H3TGXXXXLX1XXALBXCXXXXDX
167F4814

Danfoss 167F4814 - VLT HVAC Drive FC 102 (37 kW / 50 HP, IP66, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P37K) 37 KW / 50 HP,
  • Three phase, 380 - 480 VAC, (P66) IP66 / NEMA 4X Backplate
  • (H3) RFI Class A1/B (C1)
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Condition Based Monitoring CBM
  • Frame: C1
  • PROFINET MCA 120, No B Option
  • No C1 option, No D option
Model code:
FC-102P37KT4P66H3TGXXXXLX1XXALBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP37K(P37K) 37 KW / 50 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureP66(P66) IP66 / NEMA 4X Backplate
RFI FilterH3(H3) RFI Class A1/B (C1)
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseLX1XCondition Based Monitoring CBM
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC1
Height [mm]685,0
Width w/ no C options [mm]308,0
Depth [mm]311,0
Depth with Option A/B [mm]311,0
Power 110% (NO) [KW]37
kVA50.6
Power Loss NO [W]739
Continuous Current (NO) [A]73
Intermittent Current (NO) [A]80.3
Continuous Current (NO) [A]65
Intermittent Current (NO) [A]71.5

Technical data

Motor power37 kW / 50 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP66 / NEMA 4X Backplate
Frame sizeC1
RFI filterClass A1/B (EMC C1)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
Product typeFrequency converter
Continuous output current73 A
Continuous current (high line)65 A
Intermittent output current80.3 A
Apparent power50.6 kVA
Power loss739 W
Power, normal overload37 kW
Height685 mm
Width308 mm
Depth311 mm
Depth with A/B options311 mm
Net weight42.45 kg
Gross weight45.45 kg
Packed volume158.1 L
EAN5715253938288
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167F4814 are available on request. Ask for documents →

Other 37 kW / 50 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty