Danfoss VLT AQUA Drive FC 202 FC-202P3K0T4Y66H2TGX1XXLXX1XAXBXCXXXXDX
167F8092

Danfoss 167F8092 - VLT AQUA Drive FC 202 (3 kW / 4 HP, IP66, 380-480V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (P3K0) 3.0 KW / 4.0 HP,
  • Three phase, 380 - 480 VAC, (Y66) IP66 / NEMA 4X Backplate
  • RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Not coated PCB, Mains Disconnect
  • Cascade controller 2.0
  • Frame: A4
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-202P3K0T4Y66H2TGX1XXLXX1XAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingP3K0(P3K0) 3.0 KW / 4.0 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureY66(Y66) IP66 / NEMA 4X Backplate
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseLXX1Cascade controller 2.0
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeA4
Height [mm]391,0
Width w/ no C options [mm]200,0
Depth [mm]177,0
Depth with Option A/B [mm]177,0
Power 150% (HO) [KW]3
Power 110% (NO) [KW]3
kVA4.99
Power Loss HO [W]116
Power Loss NO [W]116
Continuous Current (HO) [A]7.2
Intermittent Current (HO) [A]10.8
Continuous Current (HO) [A]6.3
Intermittent Current (HO) [A]9.45
Continuous Current (NO) [A]7.2
Intermittent Current (NO) [A]7.92
Continuous Current (NO) [A]6.3
Intermittent Current (NO) [A]6.93

Technical data

Motor power3 kW / 4 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP66 / NEMA 4X Backplate
Frame sizeA4
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionMains Disconnect
Product typeFrequency converter
Continuous output current7.2 A
Continuous current (high line)6.3 A
Intermittent output current7.92 A
Continuous current (high overload)7.2 A
Apparent power4.99 kVA
Power loss116 W
Power, normal overload3 kW
Power, high overload3 kW
Height391 mm
Width200 mm
Depth177 mm
Depth with A/B options177 mm
Net weight8.36 kg
Gross weight9.096 kg
Packed volume52.4 L
EAN5715253974552
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167F8092 are available on request. Ask for documents →

Other 3 kW / 4 HP variants in VLT AQUA Drive FC 202

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.