167G2177
Danfoss 167G2177 - VLT AutomationDrive FC 302 (315 kW / 450 HP, IP21, 380-500V)
- Frequency converter
- VLT® AutomationDrive FC-302
- (N315) 315 KW / 450 HP,
- Three phase, 380 - 500 VAC, IP21 / Type 1
- RFI Filter
- Brake chopper
- Graphical LCP + USB
- Coated PCB, Fuse
- Latest release std. SW.
- Frame: E1H
- PROFIBUS DP MCA 101, No B Option
- MCB-113 Ext. Relay Card, MCB-107 24V DC backup
Model code:
FC-302N315T5E21H2BLC7XXSXXXXA0BXCXRXXD0
FC-302N315T5E21H2BLC7XXSXXXXA0BXCXRXXD0
Similar products
- Genuine Danfoss products
- Danfoss manufacturer warranty
- Reply within one business day
Product details
| Product Group | FC- | VLT® AutomationDrive FC- |
| Series | 302 | |
| Power Rating | N315 | (N315) 315 KW / 450 HP |
| Phase | T | Three phase |
| Mains Voltage | 5 | 380 - 500 VAC |
| Enclosure | E21 | IP21 / Type 1 |
| RFI Filter | H2 | RFI Filter |
| Brake - Safe Stop | B | Brake chopper |
| LCP | L | Graphical LCP + USB |
| Coating PCB | C | Coated PCB |
| Mains Option | 7 | Fuse |
| Adaptation A | X | Standard Cable Entries |
| Adaptation B | X | No adaptation |
| Software Release | SXXX | Latest release std. SW. |
| Software Language Pack | X | Standard Language Pack |
| B Option | BX | No B Option |
| C0 Option MCO | CX | No C0 option |
| C1 Option | R | MCB-113 Ext. Relay Card |
| C Option Software | XX | No software option |
| D Option | D0 | MCB-107 24V DC backup |
| Frame Size | E1H | |
| Power 150% (HO) [KW] | 315 | |
| Power 110% (NO) [KW] | 355 | |
| Power Loss HO [W] | 6178 | |
| Power Loss HO [W] | 5322 | |
| Power Loss NO [W] | 5910 | |
| Power Loss NO [W] | 6928 | |
| kVA | 416 | |
| Continuous Current (HO) [A] | 600 | |
| Intermittent Current (HO) [A] | 900 | |
| Continuous Current (HO) [A] | 540 | |
| Continuous Current (NO) [A] | 590 | |
| Intermittent Current (HO) [A] | 810 | |
| Intermittent Current (NO) [A] | 724 | |
| Continuous Current (NO) [A] | 658 | |
| Intermittent Current (NO) [A] | 649 | |
| Height [mm] | 2000,0 | |
| Width w/ no C options [mm] | 600,0 | |
| Depth [mm] | 510,0 | |
| Depth with Option A/B [mm] | 510,0 |
Technical data
| Motor power | 315 kW / 450 HP | |
| Mains voltage | 380 - 500 VAC | |
| Phase | Three-phase | |
| Protection rating | IP21 / Type 1 | |
| Frame size | E1H | |
| RFI filter | Class A2 (EMC C3) | |
| Brake chopper | Yes | |
| Safe Torque Off | Yes | |
| Control panel | Graphical LCP + USB | |
| PCB coating | Coated PCB | |
| Mains option | Integrated Fuse | |
| Product type | Frequency converter | |
| Continuous output current | 590 A | |
| Continuous current (high line) | 658 A | |
| Intermittent output current | 724 A | |
| Continuous current (high overload) | 600 A | |
| Apparent power | 416 kVA | |
| Power loss | 5910 W | |
| Power, normal overload | 355 kW | |
| Power, high overload | 315 kW | |
| Height | 2000 mm | |
| Width | 600 mm | |
| Depth | 510 mm | |
| Depth with A/B options | 510 mm | |
| Net weight | 295 kg | |
| Gross weight | 295.3 kg | |
| Packed volume | 1372.4 L | |
| EAN | 5715786020245 | |
| ECCN (US) | 3A999.a | |
Documents
Operating guides, design guides, certificates and CAD drawings for 167G2177 are available on request. Ask for documents →
Other 315 kW / 450 HP variants in VLT AutomationDrive FC 302
- 136H5644 IP00 · Class A2 · E3H
- 132X3269 IP00 · Class A2 · E3H
- 167F4798 IP00 · Class A2 · E3H
- 136H2088 IP00 · Class A2 · E3H
- 135N9335 IP00 · Class A2 · E3H
- 167G0765 IP00 · Class A2 · E3H
- 132L0932 IP00 · Class A2 · E3H
- 137H1812 IP00 · Class A2 · E3H
- 132N9739 IP00 · Class A2 · E3H
- 136H9699 IP00 · Class A2 · E3H
- 137H9097 IP00 · Class A2 · E3H
- 137H4501 IP00 · Class A2 · E3H
- 137H0951 IP00 · Class A2 · E3H
- 136X4841 IP00 · Class A2 · E3H
- 136H9712 IP00 · Class A2 · E3H
- 132H8966 IP00 · Class A2 · E3H
- 137H6068 IP00 · Class A2 · E3H
- 135U8617 IP00 · Class A2 · E3H
- 135U2712 IP00 · Class A2 · E3H
- 137L9619 IP00 · Class A2 · E3H
- 136Z0058 IP00 · Class A2 · E3H
- 132X7487 IP00 · Class A2 · E3H
- 135X7256 IP00 · Class A2 · E3H
- 135X3611 IP00 · Class A2 · E3H