Danfoss VLT AQUA Drive FC 202 FC-202P5K5T6E55HXTGXXSXSXXXXAQBPCXXXXDX
167G2483

Danfoss 167G2483 - VLT AQUA Drive FC 202 (5.5 kW / 7.5 HP, IP55, 525-600V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (P5K5) 5.5 KW / 7.5 HP,
  • Three phase, 525 - 600 VAC, IP55 / Type 12
  • No RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: A5
  • Modbus TCP MCA 122, MCB-105 Relay Card
  • No C1 option, No D option
Model code:
FC-202P5K5T6E55HXTGXXSXSXXXXAQBPCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingP5K5(P5K5) 5.5 KW / 7.5 HP
PhaseTThree phase
Mains Voltage6525 - 600 VAC
EnclosureE55IP55 / Type 12
RFI FilterHXNo RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation ASSmooth imperial cable entr
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionBPMCB-105 Relay Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeA5
Height [mm]420,0
Width w/ no C options [mm]242,0
Depth [mm]200,0
Depth with Option A/B [mm]200,0
Power 150% (HO) [KW]5.5
Power 110% (NO) [KW]5.5
kVA8.96
Power Loss HO [W]195
Power Loss NO [W]195
Continuous Current (HO) [A]9.5
Intermittent Current (HO) [A]14.2
Continuous Current (HO) [A]9
Intermittent Current (HO) [A]13.5
Continuous Current (NO) [A]9.5
Intermittent Current (NO) [A]10.5
Continuous Current (NO) [A]9
Intermittent Current (NO) [A]9.9

Technical data

Motor power5.5 kW / 7.5 HP
Mains voltage525 - 600 VAC
PhaseThree-phase
Protection ratingIP55 / Type 12
Frame sizeA5
RFI filterNone
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
Product typeFrequency converter
Continuous output current9.5 A
Continuous current (high line)9 A
Intermittent output current10.5 A
Continuous current (high overload)9.5 A
Apparent power8.96 kVA
Power loss195 W
Power, normal overload5.5 kW
Power, high overload5.5 kW
Height420 mm
Width242 mm
Depth200 mm
Depth with A/B options200 mm
Net weight12.06 kg
Gross weight12.676 kg
Packed volume39.8 L
EAN5715786023376
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167G2483 are available on request. Ask for documents →

Other 5.5 kW / 7.5 HP variants in VLT AQUA Drive FC 202

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.