Danfoss VLT AutomationDrive FC 302 FC-302P30KT6E20HXXNXXXXSXXXXALB8CXXXXDX
167G4836

Danfoss 167G4836 - VLT AutomationDrive FC 302 (30 kW / 40 HP, IP20, 525-600V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P30K) 30 KW / 40 HP,
  • Three phase, 525 - 600 VAC, (E20) IP20 / Chassis
  • No RFI Filter
  • No brake chopper
  • Numerical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: B4
  • PROFINET MCA 120, MCB-152 PROFIsafe
  • No C1 option, No D option
Model code:
FC-302P30KT6E20HXXNXXXXSXXXXALB8CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP30K(P30K) 30 KW / 40 HP
PhaseTThree phase
Mains Voltage6525 - 600 VAC
EnclosureE20(E20) IP20 / Chassis
RFI FilterHXNo RFI Filter
Brake - Safe StopXNo brake chopper
LCPNNumerical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionB8MCB-152 PROFIsafe
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeB4
Power 150% (HO) [KW]30
Power 110% (NO) [KW]37
Power Loss HO [W]600
Power Loss NO [W]740
kVA40.8
Continuous Current (HO) [A]43
Intermittent Current (HO) [A]64.5
Continuous Current (HO) [A]41
Continuous Current (NO) [A]52
Intermittent Current (HO) [A]61.5
Intermittent Current (NO) [A]59.4
Continuous Current (NO) [A]54
Intermittent Current (NO) [A]57.2
Height [mm]516,0
Width w/ no C options [mm]229,0
Depth [mm]242,0
Depth with Option A/B [mm]242,0

Technical data

Motor power30 kW / 40 HP
Mains voltage525 - 600 VAC
PhaseThree-phase
Protection ratingIP20 / Chassis
Frame sizeB4
RFI filterNone
Brake chopperNo
Safe Torque OffYes
Control panelNumerical LCP
PCB coatingUncoated
Mains optionNone
Product typeFrequency converter
Continuous output current52 A
Continuous current (high line)54 A
Intermittent output current59.4 A
Continuous current (high overload)43 A
Apparent power40.8 kVA
Power loss740 W
Power, normal overload37 kW
Power, high overload30 kW
Height516 mm
Width229 mm
Depth242 mm
Depth with A/B options242 mm
Net weight20.84 kg
Gross weight24.54 kg
Packed volume105.7 L
EAN5715786047464
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167G4836 are available on request. Ask for documents →

Other 30 kW / 40 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.