Danfoss VLT AQUA Drive FC 202 FC-202P7K5T4E66H1TGC1OXSXXXXANBXCXXXXD0
167G5973

Danfoss 167G5973 - VLT AQUA Drive FC 202 (7.5 kW / 10 HP, IP66, 380-480V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (P7K5) 7.5 KW / 10 HP,
  • Three phase, 380 - 480 VAC, (E66) IP66 / NEMA 4X
  • (H1) RFI Class A1/B (C1)
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: A5
  • EtherNet/IP MCA 121, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-202P7K5T4E66H1TGC1OXSXXXXANBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingP7K5(P7K5) 7.5 KW / 10 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE66(E66) IP66 / NEMA 4X
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AOMetric thread cable entry
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeA5
Height [mm]420,0
Width w/ no C options [mm]242,0
Depth [mm]200,0
Depth with Option A/B [mm]200,0
Power 150% (HO) [KW]7.5
Power 110% (NO) [KW]7.5
kVA11.1
Power Loss HO [W]225
Power Loss NO [W]225
Continuous Current (HO) [A]16
Intermittent Current (HO) [A]24
Continuous Current (HO) [A]14.5
Intermittent Current (HO) [A]21.8
Continuous Current (NO) [A]16
Intermittent Current (NO) [A]17.6
Continuous Current (NO) [A]14.5
Intermittent Current (NO) [A]16

Technical data

Motor power7.5 kW / 10 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP66 / NEMA 4X
Frame sizeA5
RFI filterClass A1/B (EMC C1)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
Product typeFrequency converter
Continuous output current16 A
Continuous current (high line)14.5 A
Intermittent output current17.6 A
Continuous current (high overload)16 A
Apparent power11.1 kVA
Power loss225 W
Power, normal overload7.5 kW
Power, high overload7.5 kW
Height420 mm
Width242 mm
Depth200 mm
Depth with A/B options200 mm
Net weight13.21 kg
Gross weight13.826 kg
Packed volume39.8 L
EAN5715786058934
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167G5973 are available on request. Ask for documents →

Other 7.5 kW / 10 HP variants in VLT AQUA Drive FC 202

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.