Danfoss VLT AutomationDrive FC 302 FC-302P75KT5E20H2BGCXXXSXXXXALB4CXXXXDX
167G8024

Danfoss 167G8024 - VLT AutomationDrive FC 302 (75 kW / 100 HP, IP20, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P75K) 75 KW / 100 HP,
  • Three phase, 380 - 500 VAC, (E20) IP20 / Chassis
  • RFI Filter
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: C4
  • PROFINET MCA 120, MCB-114 VLT Sensor Input
  • No C1 option, No D option
Model code:
FC-302P75KT5E20H2BGCXXXSXXXXALB4CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP75K(P75K) 75 KW / 100 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE20(E20) IP20 / Chassis
RFI FilterH2RFI Filter
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionB4MCB-114 VLT Sensor Input
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC4
Power 150% (HO) [KW]75
Power 110% (NO) [KW]90
Power Loss HO [W]1232
Power Loss NO [W]1474
kVA102
Continuous Current (HO) [A]147
Intermittent Current (HO) [A]220
Continuous Current (HO) [A]130
Continuous Current (NO) [A]160
Intermittent Current (HO) [A]195
Intermittent Current (NO) [A]195
Continuous Current (NO) [A]177
Intermittent Current (NO) [A]176
Height [mm]660,0
Width w/ no C options [mm]370,0
Depth [mm]333,0
Depth with Option A/B [mm]333,0

Technical data

Motor power75 kW / 100 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP20 / Chassis
Frame sizeC4
RFI filterClass A2 (EMC C3)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
Product typeFrequency converter
Continuous output current160 A
Continuous current (high line)177 A
Intermittent output current195 A
Continuous current (high overload)147 A
Apparent power102 kVA
Power loss1474 W
Power, normal overload90 kW
Power, high overload75 kW
Height660 mm
Width370 mm
Depth333 mm
Depth with A/B options333 mm
Net weight47.71 kg
Gross weight50.8 kg
Packed volume207.4 L
EAN5715786079595
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167G8024 are available on request. Ask for documents →

Other 75 kW / 100 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.