Danfoss VLT HVAC Drive FC 102 FC-102N710T7E5MH2TLC3XXSXXXXAXBXCXRXXD0
167G9709

Danfoss 167G9709 - VLT HVAC Drive FC 102 (710 kW / 1000 HP, IP54, 525-690V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N710) 710 KW / 1000 HP, 560kW@525- 550V, 750HP@575V, 710kW@690V
  • Three phase, 525 - 690 VAC *, IP54/Type 12+main shield
  • RFI Filter
  • Safe Stop
  • Graphical LCP + USB
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: E2H
  • No A Option, No B Option
  • MCB-113 Ext. Relay Card, MCB-107 24V DC backup
Model code:
FC-102N710T7E5MH2TLC3XXSXXXXAXBXCXRXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN710(N710) 710 KW / 1000 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE5MIP54/Type 12+main shield
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPLGraphical LCP + USB
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionRMCB-113 Ext. Relay Card
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeE2H
Height [mm]2000,0
Width w/ no C options [mm]700,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
Power 110% (NO) [KW]710
kVA872
Power Loss NO [W]10346
Power Loss NO [W]10066
Continuous Current (NO) [A]763
Intermittent Current (NO) [A]839
Continuous Current (NO) [A]730
Intermittent Current (NO) [A]803
Power Rating at 525-550V560kW
Power Rating at 575V750HP
Power Rating at 690V710kW

Technical data

Motor power710 kW / 1000 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP54/Type 12+main shield
Frame sizeE2H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP + USB
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
Product typeFrequency converter
Continuous output current763 A
Continuous current (high line)730 A
Intermittent output current839 A
Apparent power872 kVA
Power loss10346 W
Power, normal overload710 kW
Height2000 mm
Width700 mm
Depth510 mm
Depth with A/B options510 mm
Net weight1.13 kg
Gross weight1.13 kg
Packed volume1530 L
EAN5715786096837
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167G9709 are available on request. Ask for documents →

Other 710 kW / 1000 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.