Danfoss VLT AutomationDrive FC 302 FC-302N560T7E5MH2RGR7XXSXXXXAXB2CXXXXDX
167H3024

Danfoss 167H3024 - VLT AutomationDrive FC 302 (560 kW / 750 HP, IP54, 525-690V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (N560) 560 KW / 750 HP, 450kW@525- 550V, 600HP@575V, 560kW@690V
  • Three phase, 525 - 690 VAC *, IP54/Type 12+main shield
  • RFI Filter
  • Regen Terminals
  • Graphical Loc. Cont. Panel
  • Coated PCB 3C3 + Ruggedised, Fuse
  • Latest release std. SW.
  • Frame: E1H
  • No A Option, MCB-112 PTC Therm. Card
  • No C1 option, No D option
  • ATEX: II (2) G [Ex eb Gb] [Ex db Gb] / II (2) D [Ex tb Db]
Model code:
FC-302N560T7E5MH2RGR7XXSXXXXAXB2CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingN560(N560) 560 KW / 750 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE5MIP54/Type 12+main shield
RFI FilterH2RFI Filter
Brake - Safe StopRRegen Terminals
LCPGGraphical Loc. Cont. Panel
Coating PCBRCoated PCB 3C3 + Ruggedised
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionB2MCB-112 PTC Therm. Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeE1H
Power 150% (HO) [KW]560
Power 110% (NO) [KW]630
Power Loss HO [W]8069
Power Loss HO [W]7848
Power Loss NO [W]8921
Power Loss NO [W]9208
kVA681
Continuous Current (HO) [A]596
Intermittent Current (HO) [A]894
Continuous Current (HO) [A]570
Continuous Current (NO) [A]630
Intermittent Current (HO) [A]855
Intermittent Current (NO) [A]693
Height [mm]2000,0
Width w/ no C options [mm]600,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
ATEX Marking 1ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2db Gb] / II (2) D [Ex tb Db]
Power Rating at 525-550V450kW
Power Rating at 575V600HP
Power Rating at 690V560kW

Technical data

Motor power560 kW / 750 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP54/Type 12+main shield
Frame sizeE1H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB 3C3 + Ruggedised
Mains optionIntegrated Fuse
Product typeFrequency converter
Continuous output current630 A
Continuous current (high line)630 A
Intermittent output current693 A
Continuous current (high overload)596 A
Apparent power681 kVA
Power loss8921 W
Power, normal overload630 kW
Power, high overload560 kW
Height2000 mm
Width600 mm
Depth510 mm
Depth with A/B options510 mm
Net weight295 kg
Gross weight295.3 kg
Packed volume1372.4 L
EAN5715786132436
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167H3024 are available on request. Ask for documents →