Danfoss VLT HVAC Drive FC 102 FC-102N400T4E54H4TGC3XXSXXXXALB0CXXXXDX
132L6579

Danfoss 132L6579 - VLT HVAC Drive FC 102 (400 kW / 550 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N400) 400 KW / 550 HP,
  • Three phase, 380 - 480 VAC,(E54) IP54 / Type 12
  • RFI class A1 (C2)
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: E1H
  • PROFINET MCA 120, MCB-109 I/O, RTC Back-up
  • No C1 option, No D option
Model code:
FC-102N400T4E54H4TGC3XXSXXXXALB0CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN400(N400) 400 KW / 550 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterH4RFI class A1 (C2)
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionALPROFINET MCA 120
B OptionB0MCB-109 I/O, RTC Back-up
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeE1H
Power 110% (NO) [KW]400
Height [mm]2000,0
Width w/ no C options [mm]600,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
kVA516
Power Loss NO [W]8036
Power Loss NO [W]6933
Continuous Current (NO) [A]745
Intermittent Current (NO) [A]820
Continuous Current (NO) [A]678
Intermittent Current (NO) [A]746

Technical data

Motor power400 kW / 550 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeE1H
RFI filterClass A1 (EMC C2)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
FieldbusPROFINET MCA 120
Product typeFrequency converter
Continuous output current745 A
Continuous current (high line)678 A
Intermittent output current820 A
Apparent power516 kVA
Power loss8036 W
Power, normal overload400 kW
Height2000 mm
Width600 mm
Depth510 mm
Depth with A/B options510 mm
Net weight295 kg
Gross weight295.3 kg
EAN5714853461219
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132L6579 are available on request. Ask for documents →

Other 400 kW / 550 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.