Danfoss VLT HVAC Drive FC 102 FC-102P45KT7E21H5XGCXXXSXXXXA0B4CXXXXDX
137N8738

Danfoss 137N8738 - VLT HVAC Drive FC 102 (45 kW / 60 HP, IP21, 525-690V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P45K) 45 KW / 60 HP, Specific Ratings: 37kW@525-550V, 50HP@575V, 45kW@690V
  • Three phase, 525 - 690 VAC *,IP21 / Type 1
  • Marine,ruggedis RFI A2(C3)
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: C2
  • PROFIBUS DP MCA 101, MCB-114 VLT Sensor Input
  • No C1 option, No D option
Model code:
FC-102P45KT7E21H5XGCXXXSXXXXA0B4CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP45K(P45K) 45 KW / 60 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE21IP21 / Type 1
RFI FilterH5Marine,ruggedis RFI A2(C3)
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionB4MCB-114 VLT Sensor Input
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 110% (NO) [KW]45
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA62.1
Power Loss NO [W]720
Continuous Current (NO) [A]54
Intermittent Current (NO) [A]59.4
Continuous Current (NO) [A]52
Intermittent Current (NO) [A]57.2
Power Rating at 525-550V37kW
Power Rating at 575V50HP
Power Rating at 690V45kW

Technical data

Motor power45 kW / 60 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeC2
RFI filterClass A2 (EMC C3)
Brake chopperNo
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current54 A
Continuous current (high line)52 A
Intermittent output current59.4 A
Apparent power62.1 kVA
Power loss720 W
Power, normal overload45 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight53.66 kg
Gross weight57 kg
Packed volume228.1 L
EAN5715253668697
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137N8738 are available on request. Ask for documents →

Other 45 kW / 60 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.