137X8563
Danfoss 137X8563 - VLT HVAC Drive FC 102 (400 kW / 550 HP, IP21, 380-480V)
- Frequency Converter
- VLT® HVAC Drive FC-102
- (N400) 400 KW / 550 HP,
- Three phase, 380 - 480 VAC, IP21 / Type 1
- RFI Filter
- Safe Stop
- Graphical Loc. Cont. Panel
- Coated PCB, Fuse
- Latest release std. SW.
- Frame: E1H
- Modbus TCP MCA 122, No B Option
- No C1 option, MCB-117 Real time clock option
Model code:
FC-102N400T4E21H2TGC7XXSXXXXAQBXCXXXXD1
FC-102N400T4E21H2TGC7XXSXXXXAQBXCXXXXD1
Similar products
- Genuine Danfoss products
- Danfoss manufacturer warranty
- Reply within one business day
Product details
| Product Group | FC- | VLT® HVAC Drive FC- |
| Series | 102 | |
| Power Rating | N400 | (N400) 400 KW / 550 HP |
| Phase | T | Three phase |
| Mains Voltage | 4 | 380 - 480 VAC |
| Enclosure | E21 | IP21 / Type 1 |
| RFI Filter | H2 | RFI Filter |
| Brake - Safe Stop | T | Safe Stop |
| LCP | G | Graphical Loc. Cont. Panel |
| Coating PCB | C | Coated PCB |
| Mains Option | 7 | Fuse |
| Adaptation A | X | Standard Cable Entries |
| Adaptation B | X | No adaptation |
| Software Release | SXXX | Latest release std. SW. |
| Software Language Pack | X | Standard Language Pack |
| B Option | BX | No B Option |
| C0 Option MCO | CX | No C0 option |
| C1 Option | X | No C1 option |
| C Option Software | XX | No software option |
| D Option | D1 | MCB-117 Real time clock option |
| Frame Size | E1H | |
| Height [mm] | 2000,0 | |
| Width w/ no C options [mm] | 600,0 | |
| Depth [mm] | 510,0 | |
| Depth with Option A/B [mm] | 510,0 | |
| Power 110% (NO) [KW] | 400 | |
| kVA | 516 | |
| Power Loss NO [W] | 8036 | |
| Power Loss NO [W] | 6933 | |
| Continuous Current (NO) [A] | 745 | |
| Intermittent Current (NO) [A] | 820 | |
| Continuous Current (NO) [A] | 678 | |
| Intermittent Current (NO) [A] | 746 |
Technical data
| Motor power | 400 kW / 550 HP | |
| Mains voltage | 380 - 480 VAC | |
| Phase | Three-phase | |
| Protection rating | IP21 / Type 1 | |
| Frame size | E1H | |
| RFI filter | Class A2 (EMC C3) | |
| Brake chopper | No | |
| Safe Torque Off | Yes | |
| Control panel | Graphical LCP | |
| PCB coating | Coated PCB | |
| Mains option | Integrated Fuse | |
| Product type | Frequency converter | |
| Continuous output current | 745 A | |
| Continuous current (high line) | 678 A | |
| Intermittent output current | 820 A | |
| Apparent power | 516 kVA | |
| Power loss | 8036 W | |
| Power, normal overload | 400 kW | |
| Height | 2000 mm | |
| Width | 600 mm | |
| Depth | 510 mm | |
| Depth with A/B options | 510 mm | |
| Net weight | 295 kg | |
| Gross weight | 295.3 kg | |
| Packed volume | 1372.4 L | |
| EAN | 5715253873152 | |
| ECCN (US) | 3A999.a | |
Documents
Operating guides, design guides, certificates and CAD drawings for 137X8563 are available on request. Ask for documents →
Other 400 kW / 550 HP variants in VLT HVAC Drive FC 102
- 136G1005 IP00 · Class A2 · E3H
- 135U8283 IP00 · Class A2 · E3H
- 132X8457 IP00 · Class A2 · E3H
- 135U2358 IP00 · Class A2 · E3H
- 135U5252 IP00 · Class A2 · E3H
- 135U5246 IP00 · Class A2 · E3H
- 136F7197 IP00 · Class A1 · E3H
- 135X1953 IP00 · Class A1 · E3H
- 136G1028 IP00 · Class A1 · E3H
- 135U7241 IP00 · Class A2 · DB2
- 135N3965 IP00 · Class A2 · DB2
- 134X7715 IP00 · Class A1 · DB2
- 135U2898 IP20 · Class A2 · E3H
- 136U9508 IP20 · Class A2 · E3H
- 136U9504 IP20 · Class A2 · E3H
- 137G3062 IP20 · Class A2 · E3H
- 136U9501 IP20 · Class A2 · E3H
- 136U9498 IP20 · Class A2 · E3H
- 137N2008 IP20 · Class A2 · E3H
- 135X6376 IP20 · Class A2 · E3H
- 136N6862 IP20 · Class A1 · E3H
- 136U8012 IP20 · Class A2 · E3H
- 136F8225 IP20 · Class A2 · E3H