Danfoss VLT HVAC Drive FC 102 FC-102N400T4E5MH4TGC3XXSXXXXALBXCXXXXD0
167G4525

Danfoss 167G4525 - VLT HVAC Drive FC 102 (400 kW / 550 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N400) 400 KW / 550 HP,
  • Three phase, 380 - 480 VAC, IP54/Type 12+main shield
  • RFI class A1 (C2)
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: E1H
  • PROFINET MCA 120, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102N400T4E5MH4TGC3XXSXXXXALBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN400(N400) 400 KW / 550 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE5MIP54/Type 12+main shield
RFI FilterH4RFI class A1 (C2)
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeE1H
Height [mm]2000,0
Width w/ no C options [mm]600,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
Power 110% (NO) [KW]400
kVA516
Power Loss NO [W]8036
Power Loss NO [W]6933
Continuous Current (NO) [A]745
Intermittent Current (NO) [A]820
Continuous Current (NO) [A]678
Intermittent Current (NO) [A]746

Technical data

Motor power400 kW / 550 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54/Type 12+main shield
Frame sizeE1H
RFI filterClass A1 (EMC C2)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
Product typeFrequency converter
Continuous output current745 A
Continuous current (high line)678 A
Intermittent output current820 A
Apparent power516 kVA
Power loss8036 W
Power, normal overload400 kW
Height2000 mm
Width600 mm
Depth510 mm
Depth with A/B options510 mm
Net weight295 kg
Gross weight295.3 kg
Packed volume1372.4 L
EAN5715786044159
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 167G4525 are available on request. Ask for documents →

Other 400 kW / 550 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.